IM-P706-03 CTLS Issue 1
35
SP7-20 Smart Positioner
4. Changing parameter settings:
-
Quickly press and release ARROW UP to select CTCLOCKW.
5. Switching to parameter 3.3 (Return to operating level) and saving the new settings:
-
Press and hold downMODE, additionally quickly press and release ARROW UP 2×,
The following is now shown in the display:
-
ReleaseMODE,
-
Quickly press and release ARROW UP to select NV_SAVE,
-
PressENTER and hold down until the countdown goes from 3 to 0.
The new parameter setting is saved and the positioner automatically returns to the operating level. It continues
in the operating mode that was active prior to the configuration level being called up.
4.6 Setting the option modules
Setting the mechanical position indication
1. Loosen the screws for the housing cover and remove it.
2. Rotate the position indicator on the shaft to the desired position.
3. Attach the housing cover and screw it onto the housing. Tighten the screws so that they are hand-tight.
4. Attach the symbol label to mark the minimum and maximum valve positions on the housing cover.
Note: The labels are located on the inside of the housing cover.