20
File version: V1.0
ID
Parameter Meaning
Options
Description
16
Battery equalization
charging
DIS
Disable equalization charging.
ENA default
Enable equalization charging, valid when battery
type is FLd, SLd, and USER.
17
Battery equalization
charging voltage
58
Setting range 48V~58V in 0.4V steps, valid when
battery type is FLd, SLd, and USER.
18
Battery equalization
charging duration
120
Setting range 5min~900min in 5 minute steps, valid
when battery type is FLd, SLd, and USER.
19
Battery equalization
charging delay time
120
Setting range 5min~900min in 5 minute steps, valid
when battery type is FLd, SLd, and USER.
20
Battery equalization
charging interval
30
Setting range 0~30days in 1 day steps, valid when
battery type is FLd, SLd, and USER.
21
Battery equalization
charging stop-start
DIS default
Start equalization charging immediately.
ENA
Stop equalization charging immediately.
22
Energy-saving mode
DIS default
Disable energy-saving mode.
ENA
Enable energy-saving mode, when the load power
is less than 25W, the output of the inverter will
switch off after a 5-minute delay. When the load
exceeds 25W, the inverter will restart automatically.
23
Overload automatic
restart
DIS
Disable overload automatic restart, if an overload
occurs to shut down the output, the machine will
not be restored to power on again.
ENA default
Enable overload automatic restart. If an overload
occurs that shuts down the output, the machine
delays for 3 minutes before restarting the output.
After accumulating 5 times, it will not restart again.
24
Over-temperature
automatic restart
DIS
Disable over-temperature automatic restart, if
over-temperature occurs to switch off the output
machine no longer switch on the output.
ENA default
Enable over-temperature automatic restart, if over-
temperature occurs the output is switched off, it
will be switched on when the temperature drops.
25
Buzzer alarm
DIS
Disable buzzer alarm.
ENA default
Enable buzzer alarm.
26
Mode change alert
DIS
Disable alert when the status of the main input
source changes.
ENA default
Enable alert when the status of the main input
source changes.