3rd time slot end
battery discharging
Setting range: 00:00:00-23:59:00.
Time slot battery
discharging function
When the time slot battery discharging function is
enabled, the power supply mode will be switched
to UTI, and the system will switch to battery
inverter power supply only during the set discharge
period or when the mains is outaged.
YY/MM/DD. Setting range: 00:01:01-99:12:31.
Setting range: 00:00:00-23:59:59.
Charging stops when the charging current is less
than this setting (unit: A).
Discharging alarm
SOC setting
Triggers an alarm when the battery SOC is less
than the set value (unit:%, valid only when BMS
communication is normal)
Discharging cut-off
SOC setting
Stops discharging when the battery SOC is less
than the set value (unit:%, valid only when BMS
communication is normal)
Charging cut-off
SOC setting
Stops charging when the battery SOC is higher
than the set value (unit:%, valid only when BMS
communication is normal)
Switching to utility
SOC setting
Switch to utility power when the battery SOC is less
than this setting value (unit:%, valid only when BMS
communication is normal)
Swithing to inverter
output SOC setting
Switches to inverter output mode when SOC is
higher than this setting value (unit:%, valid only
when BMS communication is normal)
N-PE bonding
automatic switching
function
Disable automatic switching of N-PE connections.
Enable automatic switching of N-PE connections.
Insulation
impedance
detection
Disable detecting insulation impedance value.
Enable detecting insulation impedance value.