29
File version: V1.0
Li-ion battery
Parameter/Battery type
Ternary
LFP
User-defined
N13
N14
L16
L15
L14
USE
Over-voltage cut-off
voltage
60V
60V
60V
60V
60V
60V
Equalization charging
voltage
-
-
-
-
-
40~60V
settable
Bulk charging voltage
53.2V
57.6V
56.8V
53.2V
49.2V
40~60V
settable
Float charging
voltage
53.2V
57.6V
56.8V
53.2V
49.2V
40~60V
settable
Under-voltage alarm
voltage
43.6V
46.8V
49.6V
46.4V
43.2V
40~60V
settable
Under-voltage cut-
off voltage
38.8V
42V
48.8V
45.6V
42V
40~60V
settable
Discharging limit
voltage
36.4V
39.2V
46.4V
43.6V
40.8V
40~60V
settable
Over-discharge delay
time
30s
30s
30s
30s
30s
1~30s
settable
Equalization charging
duration
-
-
-
-
-
0~600min
settable
Equalization charging
interval
-
-
-
-
-
0~250d
settable
Bulk charging interval
120min
settable
120min
settable
120min
settable
120 m
settable
120 m
settable
10~600min
settable
If no BMS is connected, the inverter will charge according to battery voltage with a preset
charging curve. When the inverter communicates with the BMS, it will follow the BMS
instructions to perform a more complex stage charging process.
!