EasyManuals Logo

Sunfar E500-2S0015(B) User Manual

Default Icon
103 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
26 Function Parameter Table
E500 Series Universal Low-Power Inverter
Parameter
Type
Function
Code
Name
Setting Range and
Description
Minimum
unit
Default
setting
Modifica-
tion limit
Multispeed and senior running parameter group
F3.11
Under voltage
p
rotection level
180 ~ 230V /
360 ~ 460V
1
200/
400
F3.12
Overvoltage
suppression level
350 ~ 400V /
700 ~ 800V
1
360/
720
F3.13
Current
amplitude
limiting level
150 ~ 250 (%) 1 180
F3.14 Program version 1200 ~ 1299 1 1200
F3.15 Reserve
F3.16 Reserve
F3.17
Multi-speed
running mode
Units: PLC action
selection
0: No action
1: Action
2: Conditional
Tens: PLC
operating mode
selection
0: Single cycle
mode
1:Single cycle
stop mode
2: Final value
keeping mode
3: Set value
keeping mode
4: Continuous cycle
mode
1 0000
F3.18
Stage 1 running
time
0.0S~6000.0S 0.1 0.0
F3.19
Stage 2 running
time
0.0S~6000.0S 0.1 0.0
F3.20
Stage 3 running
time
0.0S~6000.0S 0.1 0.0
F3.21
Stage 4 running
time
0.0S~6000.0S 0.1 0.0
F3.22
PLC multi
-
speed
running directio
n
0000~1111H 1 0000
F3.23
PLC running
scheduled stop
0~9999(min) 1 0
F3.24
Fault
self-recovery
times
0~5 1 3
F3.25
Fault
self-recovery
time
0.0~60.0 0.1 2.0
HRW Limited
admin@hrw.hk
www.hrw.hk

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sunfar E500-2S0015(B) and is the answer not in the manual?

Sunfar E500-2S0015(B) Specifications

General IconGeneral
BrandSunfar
ModelE500-2S0015(B)
CategoryInverter
LanguageEnglish

Related product manuals