54 Function Parameter Table
E500 Series Universal Low-Power Inverter
This parameter is used to determine the display contents on the operating panel
at the monitoring status.
The monitoring parameter selection is used to determine the display content on
the LED.
The physical quantity corresponding to the display data can be referred to the
status monitoring parameter table.
This parameter is the check code for obtaining authority of inquiring and
modifying some internal parameters.
It is used to change inverter’s parameters into default value.
0: No action
1: Standard initialization
: (All parameters in F0~F6 except F0.00, F0.02, F0.05,
F0.06, F0.08, F0.11, F0.13 and F3.14 are restored to the default settings)
2: Clearing fault records
3: Complete initialization
: (all parameters in F0~F6 group except for F3.14 is
restored to default settings and fault records are cleared).
This parameter specifies allowable lower limiting voltage at the DC side when
the inverter works normally. For some occasions with low grid, it is applicable
to appropriately reduce under voltage protection level so as to ensure normal
F3.08 Monitoring parameter selection Setting range: 0 ~ 22
F3.09 Parameter inquiry and modification authority Setting range: 0 ~ 9999
F3.10 Parameter initialization Setting range: 0 ~ 9
F3.11 Under voltage protection level Setting range: 180 ~230V/360 ~460V
Running liner speed (d-8) = F3.07 X Output frequency (d-0)
Set liner speed (d-9) = F3.07 X Set frequency (d-6)