8   Grid Dispatching Function
8.1   Function Description
The Data Logger is equipped with a power control module. The module is used to receive
control commands from the grid dispatch center and send the control commands to the
monitored inverter through the RS485 port. This allows for the control of various parameters
such as active power, reactive power, and power factor, and the ability to start or stop the
inverter.
8.2   Power Control
Power regulation includes active power control and reactive power regulation.
8.2.1 Active Power
8.2.1.1 Disable Derating
When Disable Derating is selected, the inverter operates at full load.
step 1 Click Power Control > Active Power to enter the Active Power page.
step 2 Set Active Control Mode to Disable Derating, and click Save.
- - End
8.2.1.2 Remote Power Control
When the command is issued through IEC104 or MODBUS TCP protocol, set Active
Control Mode to Remote Power Control.
step 1 Click Power Control > Active Power to enter the Active Power page.
step 2 Set Active Control Mode to Remote Power Control.
73