EasyManua.ls Logo

Sungrow MVS3200-US - Page 43

Sungrow MVS3200-US
71 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
step 3 Prepare the terminals and install them tightly, where reference can be made to the
installation manual of the cable connector.
Both cooper-core cable and aluminium-core cable are applicable.
In case of copper-core cables, use copper wiring terminals.
In case of aluminium cables, use copper-to-aluminium adapter terminals.
A maximum of 2x2 output cables can be connected to the HV wiring copper bars, i.e., the
outer copper bar (shown by 1), and the inner copper bar (shown by 2).
On site, determine the number of output cables and the wiring scheme according to actual
situation.
After wiring, reliably connect the cable connector to the grounding copper bar inside the
high-voltage room according to local standards and regulations, where the fastening torque
is 60~70N.m.
System Manual 6 Electrical Installation

Table of Contents

Related product manuals