121
14
Appendix
14.1 Technical Data
table 14-1 SC1200UD&SC1375UD
Parameter SC1200UD SC1375UD
DC side parameter
Max. DC voltage
1500 V
Min. DC voltage
700 V 800 V
DC voltage range
700 1500 V 800 1500 V
Max. DC current 1935A
No. of DC inputs
1 or 10
AC sideGrid
AC output power
1320 kVA @ 30
(86) / 1200 kVA @ 45
(113 )
1512 kVA @ 30
(86) / 1375 kVA @ 45
(113 )
Max. AC current
1587 A @ 30 (86) / 1443 A @ 45 (113 )
Nominal AC voltage
480 V 550 V
AC voltage range
422 528 V 484 605 V
Nominal grid frequency / Grid fre-
quency range
50 Hz / 45 55 Hz, 60 Hz / 55 65 Hz
Max.THD of current
< 3 % (at nominal power)
DC component
< 0.5 % In
Power factor at nominal power / Ad-
justable power factor
0.99 / 1 leading - 1 lagging
Adjustable Reactive power
-100 % 100 %
Feed-in phases / Connection
phases
3 / 3
AC side (Off-Grid)
Nominal AC voltage
480 V 550 V
AC voltage range
422 528 V 484 605V