Figure 3-9. Fan Positions
System Cooling
Fans
The chassis contains four 8-cm high-performance fans. Fan speed is controlled by IPMI
depending on the system temperature. If a fan fails, the remaining fans will ramp up to full
speed. The system will continue to run with a failed fan, although it may shut down if the
heat gets too great. Replace any failed fan at your earliest convenience with the same model.
Changing a System Fan
1. Determine which fan has failed using IPMI, or if necessary, open the chassis while the
system is running. Never run the server for long without the chassis cover.
2. Push the release tab and pull the failed fan from the chassis. Fans can be replaced
while the system is running.
3. Replace the failed fan with an identical fan, available from Supermicro. Push the new
4. Power up the system and check that the fan is working properly and that the LED on the
control panel has turned off. Finish by replacing the chassis cover.