Function
Code
Name Setting Range Min. Unit Default
Modifi-
cation
FB-09
Door open/
close times
0~20 1 0 ☆
FB-10
Run main
landing door
state
0: open the door normally
1: waiting for opening the door
1 0
FB-11
Time keeping
for hall call door
opening
1~30s 1s 5s ☆
FB-12
Time keeping
for internal call
door opening
1~30s 1s 3s ☆
FB-13
Time keeping
for opening at
main landing
(main landing is
used including
Single Lift,
Group Control
,
and Lock Lift)
1~30s 1s 10s ☆
FB-14
Delay time for
open keeping
10~1000s 1s 30s ☆
FC Protect Function Parameters
FC-00
Earth short
circuit
protection
detection after
power on
0:Forbidden;
1:Allowable
1 1 ★
FC-01
Protection
selection
Bit0:Overload protection selection
0:Forbidden
1:Allowable
Bit1:Output phase-failure selection
0:Phase-failure protection
1:Phase-failure unprotected
Bit3: E053 add door-close limit judgment
0
:no new method
1:old method + old method
Bit4: door-closing limit judge light curtain
0:no re-opening
1:re-open the door
Bit5: DSP communication judgment
0:wire broken check
1:no check
Bit6: new method for parallel door block
0: use mew method
1: resume to 745 program
Bit7:reveling over-speed check
0:check
1:no check
1 1 ☆
FC-02
Overload
protection
coefficient
0.50~10.00 0.01 1.00 ☆
FC-03
Overload
pre-warning
coefficient
50~100% 1% 80% ☆
FC-04
Error self-
resetting times
0:Means that the system forbidden auto-
resetting function;
0~10
1 0 ★
FC-05
Reset interval
time
2~20s 1s 5s ★