F8-10
Power failure emergency rescue
speed
Default 0 Min. Unit 1
Setting Range
0: Motor isn’t running
1: UPS power running
2: 48V batter power
NICE 3000 supplies three ways of emergency rescue methods, details are in chapter 7.
F8-11
Car stopping torque output delay Default
0.200(asynchronous)
0.600(sync)
Min.
Unit
0.001
Setting Range 0.200~1.500s
After setting the commands of outputting brake close when the lift stops running, time for zero
speed running depends on the brake.
6.10 F9 Group Time Parameters
F9-00
Free return main oor time Default 10min Min. Unit 1min
Setting Range 0~240min
It can set the time of back to the main oor when it is free. When lift doesn’t receive car call,
hall call or any other commands, the lift will return to the main oor.
0:This function is invalidation.
F9-01
Fan and light close time Default 2min Min. Unit 1min
Setting Range 0~240min
When lift is in automatic state, no run command, the system will cut off fan and light power after
this setting time.
0:This function is invalidation.
F9-02
Longest interval time of running in
the oor
Default 45s Min. Unit 1s
Setting Range 0~45s
When lift running time is over the F9-02 setting time at border upon oors (There’s no leveling
signal then), lift will come into protection. When this parameter setting is less than 3s, this
function is invalidation.
Function code Name Default Min. Unit Setting Range
F9-03 Clock: year 2005 1 2000~2100
F9-04 Clock: month 3 1 1~12
F9-05 Clock: day 1 1 1~31
F9-06 Clock: hour 0 1 0~23
F9-07 Clock: minute 0 1 0~59