EN
53
Motor stands:
- The motor is stationary, depending on motor type. The ASM motor: if a speed
sensor is present, this signal becomes active after the end of the braking
process, consisting of generator brake and DC brake (see P48-t_stop and P55-
t_DC_brake). After the inverter has been switched on or after a reset, the motor
stands signal is inactive.
BLDC motor: The signal becomes active if the actual motor stoppage is detected
from the e.m.f. voltage.
Motor runs:
- This is the inverted motor stands signal.
Factory setting: N_rated reached
P121 relay REL2
Output value of relay REL2.
Values: - see parameter P120-relay REL1
Factory setting: overload
P125 I_warning
Value of the variable current limit for the relay output, this can be used for detecting a specific motor
load, a relay output (P120-relay REL1... P121- Relais REL2) must be configured with the current limit
function for this purpose. The value has no effect on the current limitation.
Minimum value: 0.4 A
Maximum value: 8 A
Factory setting: 0.4 A
P129 choose analog AIN
Selection of the source for AIN1
Value: U(0 - 10 V)
- PLC-compatible 0 - 10 V
I(0 - 20 mA)
- PLC-compatible 0 - 20 mA
Factory setting: U(0 - 10 V)
P135 f_rem_min
Minimum rated frequency for analogue rated frequency default AIN1 at V_e = 0 V respect. I_e = 0 mA. This
parameter is evaluated only if P129-Auswahl Analog AIN is configured for rated frequency.
By means of parameter P8-speed display, this parameter can be changed from frequency display to speed
display, the number of poles of the motor P96-no. of poles being taken into account.
Minimum value: 30 Hz
Maximum value: 4,000 Hz
Factory setting: 30 Hz
P136 f_rem_max
Maximum rated frequency for analogue rated frequency default AIN1 at V_e = 10 V respect. I_e = 20 mA.
This parameter is evaluated only if P129-Auswahl Analog AIN is configured for rated frequency.
By means of parameter P8-speed display, this parameter can be changed from frequency display to speed
display, the number of poles of the motor P96-no. of poles being taken into account.
Minimum value: 30 Hz
Maximum value: 4,000 Hz
Factory setting: 4,000 Hz