EasyManua.ls Logo

SystemAir KA HSI-2-2-S-R-50F-TB2-L2 - 3.2 Schedule for control and maintenance

SystemAir KA HSI-2-2-S-R-50F-TB2-L2
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
systemair 29
3.2 Schedule for control and maintenance
ACTIVITY
Time interval (months)
COMMENT
1/2 1 3 6 12 24
CASING
Inspection of soiling, damage and corrosion X
FAN
Inspection of soiling, damage and corrosion X
Clean the fan parts in contact with air X
FILTER
Checkforapressuredrop X
Inspection of contamination and damage X
Replacethelters X
PLATE HEAT EXCHANGER
Inspection of soiling, damage and corrosion X
Inspect the sealing of the air partition walls X
Carry out a functional test of the siphon. X
Cleaning X
ROTARY HEAT EXCHANGER
Checkthedriveoperation. X
Inspection of soiling, damage and corrosion X
Inspect the sealing of the air partition walls X
CONTROL DAMPER
Inspection of soiling, damage and corrosion X
WATER HEATING COIL (ALSO RUN AROUND COIL)
Inspection of soiling, damage and corrosion X
WATER COOLING COIL (ALSO RUN AROUND COIL)
Inspection of soiling, damage and corrosion X
Carry out a functional test of the siphon X
Cleaning X
DIRECT EXPANSION (DX)
Inspection of soiling, damage and corrosion X
Carry out a functional test of the siphon X
Cleaning X
DROPLET ELIMINATOR
Inspection of soiling, damage and corrosion X
Carry out a functional test of the siphon X
Cleaning X
SOUND ATTENUATOR
Inspection of soiling, damage and corrosion X
STEAM HUMIDIFIER
Inspection of condensate draining from chamber X Cleaning if necessary
Inspection of soiling, damage and corrosion X
Inspection of condensate draining X
Cleaning with a cleaning agent X Desinfection if necessary
Inspection of oper. and cleanliness of the dirt traps X
Inspection of build-up of deposits on the distributor X
Inspection of operation of the control valve X
HONEYCOMB HUMIDIFIER
Cleaning if shut down for more than 48 hours If necesary Clean with cleaning agent
Measuringofbacteriacountinthehumidierwater* X
Inspection of soiling, damage and corrosion X
Inspection of droplet eliminator X
Inspection of deposits on the spray nozzles X
Inspectionofdepositsofprecipitates(muck,algae,etc.)
atthebottomofthehumidiertank
X
Inspection of deposits of dirt and scale in the circulating
pump suction connection
X
Inspection of operation of the electrical conductivity
measurement elements
X
Inspection of operation of the sterilisation device. X
Inspection of oper. and cleanliness of the dirt traps X
Inspection of operation of the bleed-off device X
*ifthebacteriacount>1000CFU/ml,thewatertankmustbewashedwithcleaningagents,rinsed,driedand,ifnecessary,
disinfected.