Maintenance
Maintainthehoneycombhumidiersectionsoastopreventthegrowthandreproductionofmicroorganismsonany
component of the air handling unit / ventilation system.
Ataminimum,thewaterinthehumidiertankmustmeetthequalityrequirementsforpotablewater.Inorderto
avoid the build-up of lime deposits on the water droplet eliminator, total water hardness should not exceed 7°dH.
Prevent the growth of bacteria by means of an appropriate sterilisation system or by means of regular and
appropriate cleaning.
The bacteria count in the circulating water should not exceed the standard 1000 CFU/ml level at an incubation
temperature of 20°C ± 1°C and 36 °C ± 1°C.
AvoidtheoccurrenceofLegionellabacteriainthehumidierwater.Thetotalcountofsuchbacteriashouldnot
exceed 1 CFU/ml.
The total count of aerobic bacteria and Legionella bacteria should not exceed the level allowable according to the
regulationsinforceintheregionwheretheunitcontainingtheparticularhoneycombhumidiersectionisinstalled.
Checkthecountofbacteriainwaterinaccordancewiththeapplicableregulations.
Apply a physical or chemical method of disinfection. The selected method must be effective and not harmful to
health.
Therelativehumidityofairwithinthesystemshouldnotexceed90%.
Theadditionofchemicalstowaterforhoneycombhumidicationmustnotcompromiseairquality.
In selecting the process, consult hygiene experts.
Priortostartingupthehumidicationfunction,makesuretostartthehumidierwatersupply(startthepump)tothe
humidiercassettes–15minbeforestartingthefan.Thiswill,accordingtothemanufacturer’srecommendations,
ensurefullwettingofthehumidiercassettes.
Thedurationofthehumidieroperation,fromthestarttotheshutdown,shouldbe,ataminimum,10to15min.The
sameamountoftimeshouldalsopassbetweentheshutdownandthenextrestartofthehumidier.Ifthehumidier
runsinasequenceofshortintervals,somepartsofthehumidiermaybeneitherfullywetnorfullydry.Accordingto
themanufacturersdeclaration,thismayresultinashlikeodour.
Oncethereisnolongerademandforhumidifyingandthehoneycombhumidiersectionisshutdown(thewater
supplyisshutoff),theairhandlingunit/fanmaynotbestoppeduntilthehumidiercassettesaredry.Thenecessary
prolonged time of operation of the air handling unit is 20 minutes at a minimum.
Ifthehoneycombhumidieristobeoutofoperationforatleast24hours,drainthewaterfromthehumidiertank.
We recommended the installation of equipment for automatic water draining and drying.
Whentheairhandlingunitisoutofoperation,thehumidiersection,thehoneycombhumidierandthesiphonmust
be cleaned of all lime deposits and dirt. If the unit is not cleaned, particles of dirt harden and cause early defects in
the pump upon its restarting.
Intheeventodours(e.g.arotteneggodour)arepresentinthehumidier(andinturn,inthesupplyair),this
indicates the presence of bacteria in the water or humidifying cassettes. In such an event, shut down the air handling
unit,drainthewaterfromthehumidiersection,slideoutthecassettesanddisinfectthecassettes,thewatertank
and the section casing.
Carry out a microbiological analysis of the supply water. If the presence of bacteria is established, disinfect the water.
Ifdustoforganicoriginispresentintheairenteringthehoneycombhumidier,upgradetheltrationtoclassF7.
Settheappropriaterateofthehoneycombhumidierbleed-off.Tothisend,carryoutachemicalanalysisofthe
supply water to obtain the necessary data, as follows:
CaCO3 content (mg/l), Ca+ content (mg/l), HCO3- content (mg/l), pH value. From the water quality diagram
(providedinthehoneycombhumidiermanufacturer’sinstructions),determinethebleed-offfactor,f0.Fora
particular unit, calculate the bleed-off water volume according to the following formula:
O = f0 x E, where:
E is the amount of absorbed water (l/min)
O is the amount of bleed-off water (l/min)
Setthebleed-offwaterowratebymeansofthebleed-offvalvebyturningthevalveknobtothecorresponding
number(totheleftortotheright),thencheckthebleed-offwaterowrate(capturethebleed-offwaterina
containerofaknowncapacity,notlessthan1litre,andmeasurethecontainerllingtime).Repeatthisprocedure
until the correct bleed-off rate is achieved.