5-5-1 Automatic Gain Adjustment 
This device provides ON-LINE Auto tuning, which can quickly and precisely measure Load Inertia and 
adjust the Gain automatically. Setting is according to the table below: 
Parameter   Name  Setting Description 
Control 
Mode 
0   Auto tuning Disabled 
★ 
Cn002.2 
 
Auto tuning 
1 Enable Auto tuning 
Pe/Pi/S 
When Cn002.2 is set to 0 (Auto tuning Disabled), following Gain adjust parameters must be set.  
 
Parameter 
Signal 
Name 
Cn025 Load Inertia Ratio 
Sn211  Speed Loop Gain 1 
Sn212  Speed-loop Integral time constant 1  
Sn213  Speed loop Gain 2 
Sn214  Speed loop Integral time constant 2 
Pn310  Position Loop Gain 1 
Pn311  Position Loop Gain 2 
Pn312  Position Loop Feed-Forward Gain  
 
When Cn002.2 is set to 1 auto tuning is enabled and the Servo controller will adjust the Servo Gain in 
accordance with Cn026 (Rigidity Setting) and the measured Load Inertia Ratio by monitor parameter 
Un-19 (Load Inertia Ratio), when the Load Inertia Ratio is becomes stable, 
Then set 0 in Cn002.2 to cancel Auto tuning. At this moment, servo controller will record the measured 
Load Inertia Ratio into Cn025 (Load Inertia Ratio). 
 If servo drive is used in a applications where there is no significant load variations, then monitor Un-19 
(Load Inertia Ratio) if this is stable then it is recommended that Auto tuning is not used.