AFA4000/E VAV Airflow Controller / p.112
26. Use the ↓ button and select Exit and Save Changes. Press Enter.
The Auto Sash Controller will now go to RUN mode.
7.6.6 Setting the Auto Stop Function
1. Press and hold the Enter button for 5 seconds until the Main Menu is displayed.
2. The current Hardware and Software versions are displayed, for example 1. HW2.0 FW1.1
3. Press ↓ button, select 2. Setup and press Enter.
4. Enter the Password using the ↑ button and Enter button, the factory default is 1 0 0 1. In the
Set-Up menu, the controller will display Keypad Tones.
5. Press ↓ button, select Sash Settings and press Enter. The controller will display 1. S1 Enabled.
6. Use the ↓ button to scroll through the menu and select 9. Auto Stop. Press Enter.
7. The Auto Stop will be disabled, Press Enter then use the ↑ button to select Enabled. Press
Enter.
8. Press the ↓ button to scroll down and select Auto Stop Distance and press Enter.
9. Use the ↑ / ↓ buttons to set the required Auto stop distance above the normal position,
Press Enter.
10. Press the ↓ button to scroll down and select Auto Stop Delay and press Enter.
11. Use the ↑ / ↓ buttons to set the required Delay time before the sash returns to the normal
position after it has Auto stopped, Press Enter.
12. Use the ↓ button and select Back then Back to Set up menu. Press Enter.
13. Use the ↓ button and select Exit and Save Changes. Press Enter.
The Auto Sash Controller will now go to RUN mode.