AFA4000/E VAV Airflow Controller / p.125
Menu item
Instructions
Max Masters
Set the maximum number of AFA4000 devices on the network.
Done
Return to the Monitor config menu (section 8.1.1).
8.2 Control settings
A number of control settings must be considered to give good control of the fume cupboard
face velocity. These settings are adjustable in the ECON Configure Menu.
To access the ECON Configure Menu, navigate to Main Menu > Set up Monitor > Configure >
Econ Config.
Press the button to scroll down the menu list and press Mute to select the required option.
Note: The Configure menu is password protected. The default password is 0 0 0 0.
Note: The Monitor Set up Menu also includes Calibration and Password sub-menus which are
used by engineers to set up the system. If you enter any of the Monitor Set up sub-menus
by accident, press the
and
arrows together when the password is requested to
return to the Monitor Set up menu.