AFA4000/E VAV Airflow Controller / p.29
Function
Description
Amber Alarm LED Halo illuminated
Audible alarm sounds - can be muted by pressing the Mute
pushbutton
Sash High relay operates (if configured)
Volume Pressure
Input 2 or 3 set to Analogue Volume Pressure
Used to give volumetric output based on duct measurement using
restrictor device
Damper Feedback
Input 2 or 3 set to Analogue Damper Feedback
Used for sash position control (AFA3000) model only
3.7.4.2 Digital input functions
Function
Description
Alarm disable
When input configured as Alarm is disabled:
Alarm disabled displays in the status window
Red Alarm LED Halo illuminated
Audible alarm muted
Mute Icon shown on display
Night set-back
When input configured as Night Set-back is activated:
Night Set-back displays in the status window
Unit is driven to the VAV MIN operating position
Audible alarm muted
Mute Icon displays
Low Air alarm muted if set to Maintain Low Air
Reduce Low Air & Warning alarms active if set to Reduce Low Air
External alarm
When input configured as External alarm is activated:
Red Alarm LED Halo illuminated
External Alarm toggles on / off in the status window (when
configured)
Audible alarm sounds. Can be muted by pressing the Mute
pushbutton
External Alarm relay operates (when configured)