34
9.4. Equipment Operation upon Failure Detection and Recovery Procedure
If any malfunction is detected within the system, the buzzer sounds, the failure indicator flashes and failure
information* is displayed on the VM-3240VA’s LCD screen. The operations of other system equipment differ
when a communications error or other failures occur. The following are rough guidelines on actions to take
after such failures have been detected.
The procedure for recovery from irregularities other than communications failures is:
1. Perform failure acknowledgment.
2. Remedy the cause.
3. Perform failure reset.
Recovering from communications failures:
When a failure is detected in communications between an individual component and the VM-3240VA,
component operation can no longer be performed. First, remedy the cause of the failure.
If communication returns to normal, the original condition will automatically be restored.
* For LCD failure display, refer to page 41.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in
the Standard for Control and Communication Units for Mass Notification Systems, UL 2572 and CAN/ULC-S576,
certain programming features or options must be limited to specific values or not used at all as indicated below.
Program feature or option
Time / Interval setting
Surveillance group setting
Possible settings
Settings permitted in UL 2572
and CAN/ULC-S576
*
1
Off when no speaker is connected to the VM-3240VA or VM-3240E.
*
2
Off when no VM-3240VA or VM-3240E is connected to the VX-2000DS through DS LINK.
Permitted in UL 2572 and
CAN/ULC-S576
Battery Time
Disable / 00:00 − 23:00
DisabledN
VM-300VA On / Off OnY
External ATT/AC Time-
mains failure status
Time 00:00
Interval 100 sec
Y
Disable / 00:00 − 23:00
Emergency Control Input
Y On / Off
Emergency EV Y On / Off On
VM-3000E Y On / Off On
Battery Y On / Off On
Speaker (Open/Short) Y On / Off
On*
1
Speaker (Earth Fault) Y On / Off On
Charging Equipment Y On / Off
On*
2
General RM Y On / Off
On
On