100 ACE-tronics G9 ASD Installation and Operation Manual
Input Terminal 13 – 20 Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the ASD to any change in the 13 – 20
terminal inputs by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F145
Parameter Type — Numerical
Factory Default 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Input Terminal 17 (B12) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the B12 discrete input
terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable B12 terminal to any one
of the user-selectable functions listed in Table 7 on pg. 236.
Direct Access Number — F164
Parameter Type — Se
lection List
Factory Default Unassigned
Changeable During Run — No
Input Terminal 18 (B13) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the B13 discrete input
terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable B13 terminal to any one
of the user-selectable functions listed in Table 7 on pg. 236.
Direct Access Number — F165
Parameter Type — Se
lection List
Factory Default Unassigned
Changeable During Run — No
Input Terminal 19 (B14) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the B14 discrete input
terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable B14 terminal to any one
of the user-selectable functions listed in Table 7 on pg. 236.
Direct Access Number — F166
Parameter Type — Se
lection List
Factory Default Unassigned
Changeable During Run — No
Input Terminal 20 (B15) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the B15 discrete input
terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable B15 terminal to any one
of the user-selectable functions listed in Table 7 on pg. 236.
Direct Access Number — F167
Parameter Type — Se
lection List
Factory Default Unassigned
Changeable During Run — No
F145 F167