4 ACE-tronics G9 ASD Installation and Operation Manual
Installation Precautions
Location and Ambient Requirements
The ACE-tronics G9 ASD is intended for permanent installations only.
Installation should conform to the 2008 National Electrical Code — Article 110 (NEC)
(Requirements For Electrical Installations), all regulations of the Occupational Safety and Health
Administration, and any other applicable national, regional, or industry codes and standards.
Select a mounting location that is easily accessible, has adequate personnel working space, and
a
dequate illumination for adjustment, inspection, and maintenance of the equipment (refer to 2008
NEC Article 110-13).
DO
NOT mount the ASD in a location that would produce catastrophic results if it were to fall from
its mounting location (equipment damage or injury).
DO NOT mount the ASD in a location that would allow it to be exposed to flammable chemicals or
gases, water, solvents, or other fluids.
Avoid installation in areas where vibration, heat, humidity, dust, fibers, metal particles, explosive/
corrosive mists or gases, or sources of electrical noise are present.
The installation location shall not be exposed to direct sunlight.
Allow proper clearance spaces for installation. Do not obstruct the ventilation openings. Refer to the
section titled Installation and Connections on pg. 14 for additional information on ventilation
requirements.
The ambient operating temperature range of the ACE-tronics G9 ASD is 14° to 104° F
(-10° to 40° C).
Mounting Requirements
Only Qualified Personnel should install this equipment.
Install the unit in a secure and upright position in a well-ventilated area.
As a minimum, the installation of the equipment should conform to the 2008 Nati
onal Electrical
Code — Article 110 (NEC), OSHA, as well as any other applicable national, regional, or industry
codes and standards.
Installation practices shall conform to the latest revision of NFPA 70E Electrical Safety Requirements
for E
mployee Workplaces.
It is the responsibility of the ASD installer/maintenance personnel to ensure that the unit is installed
into an enclosure that will protect personnel against electric shock.