ACE-tronics G9 ASD Installation and Operation Manual 37
EOI Remote Mounting
The ASD may be controlled from a remotely-mounted EOI. For safety and application-specific reasons, 
some ASD installations will warrant that the operator not be in the vicinity during operation or that the 
EOI not be attached to the ASD housing. The EOI may be mounted either with or without the optional 
Remote Mounting Kit (P/N ASD-MTG-KIT). The ease of installation is enhanced by the Remote 
Mounting Kit (P/N 58333) which allows for EOI placement and easier cable routing.
Remote mounting will also allow for multiple EO
I mountings at one location if controlling and 
monitoring several ASDs from a central location is required.
The EO
I can operate up to nine feet away from the ASD. A EOI extender cable is required for remote 
mounting. The EOI extender cable is available in a nine-foot length and may be ordered through the ACE 
World Companies Customer Support Center.
The optional dust cover (P/N ASD-BPC) may be used to cover the front panel opening of the ASD 
hous
ing after removing the EOI.
Remote EOI Required Hardware
EOI Mounting Hardware
• EOI Remote-Mount Housing — P/N 58333 (included with 230-volt 40-HP and above; and with the 
460-volt 75 HP and above)
• 6-32 x 5/16” Pan Head Screw — P/N 50595 (4 ea.)
• #6 Split-Lock Washer — P/N 01884 (4 ea.)
• #6 Flat Washer — P/N 01885 (4 ea.)
Bezel Plate Mounting Hardware
• Bezel Plate — P/N 52291
• 10-32 Hex Nut — P/N 01922 (4 ea.)
• #10 Split-Lock Washer — P/N 01923 (4 ea.)
• #10 Flat Washer — P/N 01924 (4 ea.)
• Dust Cover — P/N ASD-BPC (Optional)
Extender Cable
• ASD-CAB10F: Cable, 9 ft.
EOI Installation Precautions
Install the unit securely in a well ventilated area that is out of direct sunlight using the four mounting holes 
at the rear of the EOI. The ambient temperature rating for the EOI is 14° to 104° F (-10° to 40° C).
• Select a mounting location that is easily accessible by the user.
• Avoid installation in areas where vibration, heat, humidity, dust, metal particles, or high levels of 
electrical noise (EMI) are present.
• Do not install the EOI where it may be exposed to flammable chemicals or gases, water, solvents, or 
other fluids.
• Turn on the power only after securing the front cover of the ASD.