EasyManua.ls Logo

Toshiba ACE-tronics G9 ASD - Discrete Outputs; Communications

Toshiba ACE-tronics G9 ASD
297 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACE-tronics G9 ASD Installation and Operation Manual 23
Discrete Outputs
The form-A output contacts of OUT1 (A and C), OUT2 (A and C), and the form-C output contacts
BRAKE (A, B, and C) comprise the list of discrete output terminals. The output terminals are rated for
1 A/125 VAC.
All discrete output terminals are programmable and may be set to change state upon the occurrence of a
u
ser-selected event.
10 VDC
PP is a 10 VDC/10 mA max. output for customer use.
24 VDC
P24 is a 24 VDC/200 mA max. output for customer use.
Communications
CN4 is the 2-Wire or 4-Wire serial communications port as selected by the setting of SW1.
See Program
ļƒž Communications for more information on the requirements for setting up the ASD for
ASD-to-ASD communications and for ASD-to-host (i.e., PC, PLC, etc.) communications.
Alternate I/O Terminal Board
The ACE-tronics G9 ASD may also be controlled using the 24-Volt I/O Terminal Board (optional).
The 24-Volt I/O Terminal Board (P/N 3D658344_G901) control functions operate the same as the
120-Volt I/O Terminal Board with the exception that the discrete terminal activation is carried out using
a Sink or Source method of terminal activation.
In the Sink operating mode the CC terminal is connected to a discrete input terminal to activate the
assigned function — in the Source mode a 24 VDC signal is input to a discrete input terminal to
activate the assigned function.
There are no software changes required to use the 24-Volt I/O Terminal Board.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com