ACE-tronics G9 ASD Installation and Operation Manual 79
Direct Access Information
The ACE-tronics G9 ASD has the ability to allow the user direct access to the motor control functions.
There are two ways in which the motor control parameters may be accessed for modification: Program
Direct Access Applicable Parameter Number or Program Applicable Menu Path. Both methods
access the parameter via the Program mode. Once accessed, the parameter may be viewed or changed.
The Pr
ogram mode allows the user to develop an application-specific motor-control profile. Motor
control functions may be set to accommodate application-specific power and timing requirements.
The configurable parameters of the P
rogram mode that have user-accessible Parameter Numbers are
listed and described below. The parameters that do not have a Direct Access number and are accessible via
the Program mode menu hierarchy only are listed and described on pg. 57.
Note: T
he setup procedures included within this section may require a Reset before performing the
procedure. Application-specific settings may then be performed. The pre-reset conditions may
be saved (see F007).
Note: Co
mmunications setting changes will require that the power be removed and then re-applied
for the changes to take effect.
Direct Access Parameters/Numbers
Automatic Acceleration/Deceleration
Program Fundamental Acc/Dec 1
This parameter is used to enable automatic acceleration and deceleration rates
in accordance with the applied load.
The adjusted acceleration and deceleration times range from 12.5% to 800% of
t
he programmed values for Acceleration Time 1 — UP/DOWN Frequency
Accel Time (F009) and Deceleration Time 1 — UP/DOWN Frequency Decel
Time (F010).
Settings:
Manual
Automatic ACC/DEC
Automatic ACC Only
Note: The
motor and the load must be connected prior to selecting
Automatic Acceleration/Deceleration.
Direct Access Number — F000
Parameter Type — Selection List
Factory Default — Manual
Changeable During Run — No
Automatic Torque Boost
Program Fundamental Motor Set 1
This parameter allows the ASD to adjust the output torque in accordance with
the applied load automatically. When enabled, an Autotune is performed — the
motor should be connected before performing an Autotune.
Settings:
Disabled
Automatic Torque Boost + Autotuning
Sensorless Vector Control + Autotuning
Direct Access Number — F001
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
F000 F001