272 ACE-tronics G9 ASD Installation and Operation Manual
Cable/Terminal/Torque Specifications
Installation should conform to the 2008 National Electrical Code Article 110 (NEC) (Requirements for
Electrical Installations), all regulations of the Occupational Safety and Health Administration, and any
other applicable national, regional, or industry codes and standards.
Note: T
he following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the ACE-tronics G9 ASD. Application-specific applicables,
wire insulation type, conductor material, and local and regional regulations are but a
few of the considerations when selecting the actual lug and wire type to be used with the
ASD.
Note: Cabl
e/Terminal specifications are based on the rated current of the ASD.
The specifications Do Not include the 10% Service Factor.
Note: Use only 75° C copper wire/cable for motor and power connections.
For additional installation information see the section titled Installation and Connections on pg. 14.
Note: (*) Indicates that the item is one of a set of two parallel cables.
Table 21. 230-Volt ACE-tronics G9 ASD Cable/Terminal/Torque Specifications.
Model
Number
MCP Rating
(Amps)
Typical Wire/Cable
Size
Lug Size Range
Terminal
Board
Torque
AWG or kcmil
Input/Output Power
Wire-Size/Lug-Capacity for
Input/Output Power
TB1 – 4
Terminals
3Ø-Input
3Ø-Output
Recommended Maximum 3Ø-Input 3Ø-Output
In-Lbs./Nm
ACEG92000
15 14
10 14 to 8
20
(3-core shield)
5.3/0.6
11.5/1.3
ACEG92001
ACEG92002
ACEG92003
30
12
ACEG92005 10
ACEG92007
50
8 8 12 to 8 17.7/2.0
ACEG92010
6
4 10 to 4
21/2.4ACEG92015 75
3 8 to 3
ACEG92020 100 4
ACEG92025 125 2 2 12 to 1/0 4 to 1/0 50/5.7 53/6
ACEG92030 150 1
4/0 6 to 250 2 to 300 275/31 168/19
ACEG92040 175 1/0
ACEG92050 200 3/0
ACEG92060 250 4/0
ACEG92075 300 *3/0 *4/0
6 to 250 275/31
ACEG92100 400 *250 *250