ACE-tronics G9 ASD Installation and Operation Manual 135
External Fault Stopping Method
Program Crane/Hoist External Fault
In a multiple ASD configuration a faulted ASD signals the remaining ASDs,
via a discrete input terminal, that a fault has occurred and shuts down the non-
faulted ASDs. The non-faulted ASDs experience an External Fault.
This parameter selects the stopping method in the event that a Ext
ernal Fault
is incurred.
Settings:
Coast Stop
Deceleration Stop
DC Injection Braking Stop
Direct Access Number — F280
Parameter Type — Se
lection List
Factory Default Coast Stop
Changeable During Run — No
Limit-Switch Stopping Method
Program Crane/Hoist Limit Switch Control
This parameter determines the method used to stop the motor if the Stop
command is initiated via a limit switch.
Settings:
Coast Stop
Deceleration Stop
DC Injection Braking Stop
Direct Access Number — F282
Parameter Type — Selection List
Factory Default Deceleration Stop
Changeable During Run — No
Deceleration Time at Slow-Speed-Limit UP
Program Crane/Hoist Limit Switch Control
Closure of the Upper-Limit Slow-Speed Limit-Switch implements the
modified Upper-Limit Speed (F294) and Deceleration Time (F283) settings.
This parameter sets the time to reach the modified Lower-Limit Slow Speed.
Direct Access Number — F283
Parameter Type — Numerical
Factory Default 1.5
Changeable During Run — No
Minimum — 0.1
Maximum — 1.5
Units — Seconds
Stopping Time at Stop Limit-Switch UP
Program Crane/Hoist Limit Switch Control
A Stop command is initiated upon activation of the Upper-Limit Stop Limit-
Switch.
This parameter sets the Decel rate to be used upon activation of the Upper-
Limit Stop Limit-Switch.
Direct Access Number — F284
Parameter Type — Numerical
Factory Default 1.5
Changeable During Run — No
Minimum — 0.0
Maximum — 25.0
Units — Seconds
Deceleration Time At Slow-Speed Limit-Switch DOWN
Program Crane/Hoist Limit Switch Control
Closure of the Lower-Limit Slow-Speed Limit-Switch implements the
modified Lower-Limit Slow Speed (F293) and Deceleration Time
(F285)
settings.
This parameter sets the time to reach the modified Lower-Limit Slow Speed.
Direct Access Number — F285
Parameter Type — Numerical
Factory Default 1.5
Changeable During Run — No
Minimum — 0.0
Maximum — 25.0
Units — Seconds
F280 F285