190 ACE-tronics G9 ASD Installation and Operation Manual
MON 1 Voltage/Current Output Switching
Program Terminal Analog Output Terminals
This parameter is used to set the output signal type of the MON1 output
terminal.
Settings
-10 V – +10 V
0 – 10 V
0 – 20 mA
Direct Access Number — F688
Parameter Type — Selection List
Factory Default 0 – 10V
Changeable During Run — Yes
MON 1 Output Gradient Characteristic
Program Terminal Analog Output Terminals
This parameter sets the output response polarity of the MON1 output terminal.
The MON1 output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See parameter F672 for additional information on this setting.
Settings:
Minus (Negative Gradient)
Plus (Positive Gradient)
Direct Access Number — F689
Parameter Type — Selection List
Factory Default Plus
Changeable During Run — Yes
MON 1 Bias Adjustment
Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the MON1 terminal.
Set the assigned function of parameter F672 to zero and then set this parameter
to a zero output.
See parameter F672 for additional information on this setting.
Direct Access Number — F690
Parameter Type — N
umerical
Factory Default 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — 100.0
Units — %
MON 2 Voltage/Current Output Switching
Program Terminal Analog Output Terminals
This parameter is used to set the output signal type of the MON2 output
terminal.
See parameter F674 for additional information on this setting.
Settings
-10 V – +10 V
0 – 10 V
0 – 20 mA
Direct Access Number — F691
Parameter Type — Selection List
Factory Default 0 – 10V
Changeable During Run — Yes
MON 2 Output Gradient Characteristic
Program Terminal Analog Output Terminals
This parameter sets the output response polarity of the MON2 output terminal.
The MON2 output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See parameter F672 for additional information on this setting.
Settings:
Minus (Negative Gradient)
Plus (Positive Gradient)
Direct Access Number — F692
Parameter Type — Selection List
Factory Default Plus
Changeable During Run — Yes
F688 F692