ACE-tronics G9 ASD Installation and Operation Manual 203
Communications Option (DeviceNet/Profibus) Setting 2
Program Communications Communication
While using the DeviceNet/Profibus communications protocol, parameters
F831F836 allow the user to select the ASD memory location that holds the
Command/Frequency/Monitoring instructions to be applied to the ASD for
C
ommunications Option Settings 27, respectively.
See the DeviceNet Option Instruction Manual (P/N 58683) for additional
information on this parameter.
Settings:
Disabled
FA06 (ALCAN Command 1)
FA23 (ALCAN Command 2)
FA07 (ALCAN Frequency Command, 0.01 Hz)
FA33 (Torque Command, 0.01%)
FA50 (Terminal Output)
FA51 (Analog Output Data from Comm. [FM])
FA52 (Analog Output Data from Comm. [AM])
F601 (Stall Prevention Level, %)
F441 (Power Running Torque Limit 1 Level, 0.01%)
F443 (Dynamic Braking Torque Limit 1 Level, 0.01%)
F460 (Speed Loop Proportional Gain)
F461 (Speed Loop Stabilization Coefficient)
Direct Access Number — F831
Parameter Type — Se
lection List
Factory Default 0000h
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 3
Program Communications Communication
Same as F831. See F831 for information on this parameter
Direct Access Number — F832
Parameter Type — Selection List
Factory Default 0000h
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 4
Program Communications Communication
Same as F831. See F831 for information on this parameter
Direct Access Number — F833
Parameter Type — Selection List
Factory Default 0000h
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 5
Program Communications Communication
Same as F831. See F831 for information on this parameter
Direct Access Number — F834
Parameter Type — Selection List
Factory Default 0000h
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 6
Program Communications Communication
Same as F831. See F831 for information on this parameter
Direct Access Number — F835
Parameter Type — Selection List
Factory Default 0000h
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 7
Program Communications Communication
Same as F831. See F831 for information on this parameter
Direct Access Number — F836
Parameter Type — Selection List
Factory Default 0000h
Changeable During Run — Yes
F831 F836