226 ACE-tronics G9 ASD Installation and Operation Manual
Virtual Input Terminal Selection 1
Program Terminal Input Terminals
This parameter is used to set the functionality of the Virtual Input Terminal 1.
As a virtual terminal, it exists only in memory and is considered to always be in
its True state (activated).
It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable Virtual Input Terminal 1 terminal to
one of the functions that are listed in Table 7 on pg. 236.
In addition, the input terminal must be specified as N
ormally Open or
Normally Closed.
Direct Access Number — F973
Parameter Type — Selection List
Factory Default Unassigned
Changeable During Run — No
Virtual Input Terminal Selection 2
Program Terminal Input Terminals
This parameter is used to set the functionality of the Virtual Input Terminal 2.
As a virtual terminal, it exists only in memory and is considered to always be in
its True state (activated).
It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable Virtual Input Terminal 2 terminal to
one of the functions that are listed in Table 7 on pg. 236.
In addition, the input terminal must be specified as N
ormally Open or
Normally Closed.
Direct Access Number — F974
Parameter Type — Selection List
Factory Default Unassigned
Changeable During Run — No
Virtual Input Terminal Selection 3
Program Terminal Input Terminals
This parameter is used to set the functionality of the Virtual Input Terminal 3.
As a virtual terminal, it exists only in memory and is considered to always be in
its True state (activated).
It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable Virtual Input Terminal 3 terminal to
one of the functions that are listed in Table 7 on pg. 236.
In addition, the input terminal must be specified as N
ormally Open or
Normally Closed.
Direct Access Number — F975
Parameter Type — Selection List
Factory Default Unassigned
Changeable During Run — No
Virtual Input Terminal Selection 4
Program Terminal Input Terminals
This parameter is used to set the functionality of the Virtual Input Terminal 4.
As a virtual terminal, it exists only in memory and is considered to always be in
its True state (activated).
It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable Virtual Input Terminal 4 terminal to
one of the functions that are listed in Table 7 on pg. 236.
In addition, the input terminal must be specified as N
ormally Open or
Normally Closed.
Direct Access Number — F976
Parameter Type — Selection List
Factory Default Unassigned
Changeable During Run — No
F973 F976