EasyManua.ls Logo

Toshiba ACE-tronics G9 ASD - Page 246

Toshiba ACE-tronics G9 ASD
297 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
236 ACE-tronics G9 ASD Installation and Operation Manual
Table 7. Discrete Input Terminal Assignment Selections and Descriptions.
Sel. No.
Terminal Selection Descriptions
NO NC
01Unassigned — No operation.
23Forward — Provides a Forward run command.
45Reverse — Provides a Reverse run command.
67Standby — Enables the Forward and Reverse operation commands.
89ResetResets the device and any active faults.
10 11 Preset Speed 1Preset Speed 1 is used as the LSB of the 4-bit nibble that is used to select a Preset Speed.
12 13 Preset Speed 2Preset Speed 2 is used as the second bit of the 4-bit nibble that is used to select a Preset Speed.
14 15 Preset Speed 3Preset Speed 3 is used as the third bit of the 4-bit nibble that is used to select a Preset Speed.
16 17 Preset Speed 4Preset Speed 4 is used as the MSB of the 4-bit nibble that is used to select a Preset Speed.
18 19
Jog Run This terminal activates a Jog for the duration of the activation. The Jog settings may be configured at
F260F262.
20 21
Emergency Off — Terminates the output signal from the ASD and may apply a brake if so configured. The braking
method may be selected at F603.
22 23
DC Braking Upon activation the ASD outputs a DC current that is injected into the windings of the motor to
quickly brake the motor.
24 25
Accel/Decel Switching 1/Accel/Decel Switching 2 — Activating combinations of discrete input terminals
Accel/Decel Switching 1 and 2 allow for the selection of Accel/Decel profiles 1 – 4 as shown below.
See F504 for additional information on this terminal setting.
26 27
28 29
V/f Switching 1/V/f Switching 2 — Activating combinations of discrete input terminals V/f Switching 1 and 2
allow for the selection of a V/f switching profile as listed below.
30 31
Note: NO/NC = Normally Open/Normally Closed. Selection numbers are used when selecting using communications.
A/D SW Terminal
A/D Profile Selection
#1 #2
00 1
01 2
10 3
11 4
1=Terminal Activated
The settings of the A/D selections 1 – 4 are
performed at F009/F010, F500/F501, F510/
F511, and F514/F515, respectively.
Accel/Decel profiles are comprised of the Accel/
Decel settings, Pattern, and Switching
Frequency.
V/f Switching Terminal
V/f Selection
#1 #2
00 1
01 2
10 3
11 4
1=Terminal Activated
The 1–4 settings of the V/f Switching selections
are performed at parameters F170F181.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

Table of Contents