Loading...
258 ACE-tronics G9 ASD Installation and Operation Manual
Overheat During
Deceleration
OC2P Cooling fan inoperative.
Ventilation openings are obstructed.
Internal thermistor is disconnected.
Deceleration time is too short.
DC Injection current is too high.
ASD or the motor is improperly matched to the application.
Overheat During
Run
OC3P Cooling fan inoperative.
Ventilation openings are obstructed.
Internal thermistor is disconnected.
Improper V/f setting.
ASD or the motor is improperly matched to the application.
Over-Torque OT A torque requirement by the load in excess of the setting of F616 or
F617 for a time longer than the setting of F618.
The ASD is improperly matched to the application.
The load is obstructed.
Over-Voltage
During
Acceleration
OP1 Motor running during restart.
Over-Voltage
Du
ring
Deceleration
OP2 Deceleration time is too short.
DBR value is too high.
DBR required (DBR setup required).
Stall protection is disabled.
3-phase input voltage is out of specification.
Input reactance required.
Over-Voltage
Du
ring Run
OP3 Load fluctuations.
3-Phase input voltage out of specification.
DBR required or DBR setup is incomplete.
RAM Fault ERR2 Internal RAM malfunction.
ROM Fault ERR3 Internal ROM malfunction.
Speed Error E-13 Result of a motor speed that is greater than the commanded speed when
using an encoder for speed control.
Improper encoder connection or setup information.
Defective encoder.
Step Out
(for PM Motor
Only)
SOUT
Motor shaft is locked.
Output phase is open.
Operating a reciprocating load.
LCD Screen LED Screen Possible Causes
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com