ACE-tronics G9 ASD Installation and Operation Manual 19
Figure 4. The Grounding Capacitor 
Switch is used on typeforms 230-volt 
0.5 HP to 10 HP and the 25 and 30 HP/
460-Volt 1.0 HP to 250 HP. 
The value may be set to Maximum 
(default setting) or to Zero by pushing or 
pulling the switch actuator, respectively.
Figure 5. The Grounding Capacitor 
Switch is used on typeforms 230-volt 
15 HP to 20 HP and the 40 HP to 
60 HP/460-Volt 30 HP to 100 HP. 
The value may be set to Large 
(default setting) or Small by pushing 
or pulling the switch actuator, 
respectively.
Figure 6. The Grounding Capacitor Bar is 
used on typeforms 230-volt 75 HP and the 100 
HP/460-Volt 125 HP and the 150 HP. 
The value may be set to Small (default setting) 
or Large by connecting or disconnecting the 
switching bar, respectively.
Figure 7. The Grounding Capacitor Screw is 
used on typeforms 460-volt 175 HP and above. 
The value may be set to Small (default setting) 
or Large by placing the screw in the A position 
or by placing the screw in the B position, 
respectively.