ACE-tronics G9 ASD Installation and Operation Manual 25
Table 4. ACE G9-120V-PCB Default Assignment Terminal Names and Functions.
Terminal
Name
Input/Output
Default Function
(Also See
Terminal Descriptions on pg. 26)
Circuit Config.
F
Discrete Input
Apply
120 VAC to
activate.
Forward Run Command Multifunctional programmable discrete input.
Figure 10 on pg. 29.
R
Reverse Run Command Multifunctional programmable discrete input.
I1
Input 1 Multifunctional programmable discrete input.
I2
Input 2 Multifunctional programmable discrete input.
I3
Input 3 Multifunctional programmable discrete input.
I4
Input 4 Multifunctional programmable discrete input.
I5
Stop Limit-Switch Forward Multifunctional programmable discrete input.
I6
Stop Limit-Switch Reverse — Multifunctional programmable discrete input.
OUT1
Switched
Ou
t
p
ut
Brake Failure — Multifunctional programmable discrete output.
Figure 16 on pg. 29.
OUT2 Brake Release Multifunctional programmable discrete output.
BRAKE-A BRAKE relay (N.O.).
Figure 19 on pg. 29.BRAKE-B BRAKE relay (N.C.).
BRAKE-C BRAKE relay (Common).
RR
Analog Input
Multifunctional programmable analog input. (0.0 to 10 VDC input). Figure 11 on pg. 29.
RX Multifunctional programmable analog input (±10 VDC input). Figure 12 on pg. 29.
V/I
(Select V
or
I via
SW2)
V
Multifunctional programmable isolated analog voltage input (0 to 10
VDC input).
Figure 13 on pg. 29.
Frequency Mode 2 (Default Setting) I —Multifunctional programmable
isolated analog current input (4 [0] to 20 mADC input — 0 Hz to Maximum
Frequency).
AM
Analog Output
Output Current
Vo l ta ge output that is proportional to the output current of
the ASD or to the magnitude of the function assigned to this terminal (see
Table 8 on pg. 240 for assignment listing).
Figure 18 on pg. 29
FM
Output Frequency
Current or Vo l ta ge output that is proportional to the
output frequency of the ASD or to the magnitude of the function assigned to
this terminal (see Table 8 on pg. 240). Select Current or Voltage at F681.
P24
DC Output
24 VDC output (200 mA max.). Figure 14 on pg. 29.
PP 10.0 VDC/10 mA voltage source for the external use (e.g., potentiometer). Figure 15 on pg. 29.
FP Pulsed Output
Frequency Pulse — Multifunctional programmable output pulse train of a
frequency based on the output frequency of the ASD (see Table 8 on pg. 240).
Figure 17 on pg. 29.
IICC
Return for the isolated V/I input terminal.
Do Not connect to
Earth Gnd or to each
other.
CC
Return for the AM, FM, RR, RX, P24, and the PP analog terminals.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com