ACE-tronics G9 ASD Installation and Operation Manual 35
LCD Screen
The LCD screen is the primary user input/output information center. Parameter settings may be viewed or
changed using the LCD screen module of the EOI. To view or change a parameter setting using the LCD
screen, press the Mode key until the Program menu is displayed. Turn the Rotary Encoder until the
desired Primary Menu item (see pg. 57) is within the cursor block. Press the R
otary Encoder to select
the item from the Primary Menu (repeat the press-to-select function for sub-menu items).
See the section titled Default Setting Changes on pg. 40 for more information on changing parameter
settings.
Upon reaching the desired parameter selection the current setting may be viewed, or selected and changed
by pressing the Rotary Encoder — the setting will take on the reverse video format (dark background/
light text). Turn the Rotary Encoder to change the parameter setting. Press the ESC key while the new
parameter setting is in the reverse video mode to exit the selection without saving the change or press the
Rotary Encoder while the parameter setting is in the reverse video mode to accept the new setting.
Repeated ES
C key entries at any time takes the menu back one level each time the ESC key is pressed
until the Frequency Command screen is reached. Further ESC entries will toggle the system to and from
the Frequency Command screen and the EOI Command menu.
Note: Chang
es carried out from the EOI Command screen will be effective for EOI-
controlled ASD operation only. See the section titled EOI Command Mode on pg. 53 for
additional information on EOI Command Mode operations.
Primary Menus of the LCD Screen
The three primary LCD screens are displayed while accessing the associated operating modes: the
Frequency Command, Monitor, and Program Menu screens.
Figure 23. Mo
nitor Screen (see pg. 54 for more on the Monitor Screen).
Figure 24. Program Menu Screen (see pg. 57 for more on the Program Menu Screen).
Speed Reference %
Speed Reference Hz
User-Selected
Monitored Parameters
Not-Ready-to-Run
Indicator (ST Activation Required)
Ready-to-Run Indicator
Appears When ST Is Activated
(See Main Monitor Selections
on pg. 56)
Figure 22. Frequency Command Screen.
Forward Run Active
Reverse Run Active
Discrete I/O Terminal
Status or Alarm Condition
See F110
Item Number 1 of 43
Speed at Trip (if applicable)
Active Frequency
Active DC Bus Voltage
Monitored items
Command
Active Output Current
ASD Output Voltage
Screen Name
(Only 5 Items Listed)
Primary Menu Items
Screen Name
Item Number 1 of 15
Program Menu items
{
(Only 5 Items Listed)