94 P9 ASD Installation and Operation Manual
Output Terminal 3 (FL) Function
Program Ter mi nal Output Terminals
This parameter is used to set the functionality of the FL output terminals to one
of the user-selectable functions listed in
Table 9 on pg. 251.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
Direct Access Number — F132
Parameter Type — Selection List
Factory Default Fault (All)
Changeable During Run — No
Output Terminal 4 (OUT3) Function
Program Ter mi nal Output Terminals
This parameter is used to set the functionality of the OUT3 discrete output
terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable OUT3 terminal to one of
the user-selectable functions listed in
Table 9 on pg. 251.
Note: The Expansion IO Card Option 1 option board (P/N ETB003Z)
is required to use this terminal.
See the Expansion IO Card Option 1 Instruction Manual (P/N 58685) for
additional information on the function of this terminal.
Direct Access Number — F133
Parameter Type — Selection List
Factory Default Always OFF
Changeable During Run — No
Output Terminal 5 (OUT4) Function
Program Ter mi nal Output Terminals
This parameter is used to set the functionality of the OUT4 discrete output
terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable OUT4 terminal to one of
the user-selectable functions listed in
Table 9 on pg. 251.
Note: The Expansion IO Card Option 1 option board (P/N ETB003Z)
is required to use this terminal.
See the Expansion IO Card Option 1 Instruction Manual (P/N 58685) for
additional information on the function of this terminal.
Direct Access Number — F134
Parameter Type — Selection List
Factory Default Always OFF
Changeable During Run — No