P9 ASD Installation and Operation Manual 151
(Virtual Linear Pump) Sleep Timer Delay
Virtual Linear Pump Sleep Timer Setting
During a properly configured Virtual Linear Pump operation, and once
enabled at
F382, this parameter establishes the time that system operation will
be allowed to operate within the (Virtual Linear Pump) Minimum threshold
before the ASD output to the motor is terminated.
See F382 for additional information on this parameter.
Direct Access Number — F383
Parameter Type — Numerical
Factory Default 300
Changeable During Run — Yes
Minimum — 1
Maximum — 63335
Units — Seconds
(Virtual Linear Pump) Direct Operation Command Value
Program Virtual Linear Pump Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation while operating
in the Direct mode and using the EOI for system control, this parameter
establishes the Virtual Linear Pump level.
This parameter setting is effective ONLY while operating in the Direct mode
and while receiving a command from the EOI. The end value of this parameter
setting appears in the Frequency Command screen as shown below.
Direct Access Number — F384
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Yes
Minimum — 10
Maximum — 165
(Virtual Linear Pump) Auto Start-Stop Mode
Virtual Linear Pump Auto Start-Stop Mode Enable
During a properly configured Virtual Linear Pump operation, this parameter
Enables/Disables the ability of the system to receive transducer input to
manage system starts and stops as it pertains to the process variable.
This parameter is also used to select the ASD response (Stop or Start) upon
meeting the criteria of
F388 and F389 settings.
On Forward = Run ASD while measured signal is F388 setting and stop
ASD upon reaching F389 setting.
On Reverse = Run ASD while measured signal is F389 setting and stop ASD
upon reaching F388 setting.
Settings:
0 — Off
1 — On Forward
2 — On Reverse
Direct Access Number — F385
Parameter Type — Selection List
Factory Default Off
Changeable During Run — Yes
WARNING
The Auto Start-Stop operating mode may result in the
unexpected Start or Stop of the motor. Signs to this effect are
to be posted at the location of the motor/pump.