154 P9 ASD Installation and Operation Manual
(Virtual Linear Pump) Transducer Maximum Reading
Program Virtual Linear Pump Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the maximum level of the transducer range for Virtual Linear
Pump operation.
Direct Access Number — F393
Parameter Type — Numerical
Factory Default 0
Changeable During Run — Yes
Minimum — -3276.7
Maximum — 3276.7
(Virtual Linear Pump) Minimum
Program Virtual Linear Pump Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the minimum setpoint within the Virtual Linear Pump operating
domain.
Direct Access Number — F394
Parameter Type — Numerical
Factory Default 10
Changeable During Run — Yes
Minimum — 10
Maximum — 165
(Virtual Linear Pump) Maximum
Program Virtual Linear Pump Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the maximum setpoint within the Virtual Linear Pump operating
domain.
Direct Access Number — F395
Parameter Type — Numerical
Factory Default 10
Changeable During Run — Yes
Minimum — 10
Maximum — 165
(Virtual Linear Pump) Command Source
Program Virtual Linear Pump Virtual Linear Pump Settings
During Direct mode or the Process Hold mode operation, this parameter sets
the Virtual Linear Pump command source.
Note: If Process Hold is selected at F390, selecting V/I here will result
in an error message.
Settings:
0 — EOI
1 — *V/I
2 — RR
3 — Communication Board
Direct Access Number — F396
Parameter Type — Selection List
Factory Default EOI
Changeable During Run — No