P9 ASD Installation and Operation Manual 155
(Virtual Linear Pump) Process Hold Operation Command
Value via the EOI
Program Virtual Linear Pump Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation while operating
in the Process Hold mode and using the EOI for system control, this parameter
establishes the Virtual Linear Pump level.
This parameter setting is effective ONLY while operating in the Process Hold
mode and while receiving a command via the EOI. The end value of this
parameter setting appears in the Frequency Command screen as shown below.
Direct Access Number — F397
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Yes
Minimum — F403 Setting
Maximum — F393 Setting
(Virtual Linear Pump) Low Frequency Limit
Program Virtual Linear Pump Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the Virtual Linear Pump Low Frequency Limit.
Direct Access Number — F398
Parameter Type — Numerical
Factory Default 15
Changeable During Run — Yes
Minimum — 1.00
Maximum — 60.00
Units — Hz
Autotuning 1
Program Motor Vector Motor Model
This parameter sets the Autotune command status.
Selecting Reset Motor Defaults for this parameter sets parameters F410, F411,
F412, and F413 to the factory default settings.
If selecting Autotune on Run Command, Autotune Initiated by Input
Terminal, or Autotune of Detail Parameters for this parameter, set the Base
Frequency, Base Frequency Voltage, and the Motor Rated Revolutions to
the nameplated values of the motor to achieve the best possible Autotune
precision.
Settings:
0 — Autotune Disabled
1 — Reset Motor Defaults
2 — Enable Autotune on Run Command
3 — Autotuning by Input Terminal Signal (see Table 6 on pg. 245)
4 — Motor Constant Auto Calculation
Direct Access Number — F400
Parameter Type — Selection List
Factory Default Autotune Disabled
Changeable During Run — No
F397 F400