156 P9 ASD Installation and Operation Manual
Slip Frequency Gain
Program Motor Vector Motor Model
This parameter provides a degree of slip compensation for a given load. A
higher setting here decreases the slip allowed for a given load/ASD output ratio.
Direct Access Number — F401
Parameter Type — Numerical
Factory Default 70
Changeable During Run — Yes
Minimum — 0
Maximum — 150
Units — %
Autotuning 2
Program Motor Vector Motor Model
This parameter introduces a thermal element into the autotuning equation and is
used to automatically adjust the Autotune parameter values as a function of
increases in the temperature of the motor.
Settings:
0 — Off
1 — Self-Cooled Motor Tuning
2 — Forced Air Cooled Motor Tuning
Direct Access Number — F402
Parameter Type — Selection List
Factory Default Off
Changeable During Run — No
(Virtual Linear Pump) Transducer Minimum Reading
Program Virtual Linear Pump Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the minimum level of the transducer range for Virtual Linear
Pump operation.
Direct Access Number — F403
Parameter Type — Numerical
Factory Default 0
Changeable During Run — Yes
Minimum — -32767
Maximum — 32767
F401 F403