216 P9 ASD Installation and Operation Manual
ASD-to-ASD Communications (RS485 2-wire)
Program Communications Communication Settings
The function of this parameter is two-fold:
1) In a Master/Follower configuration and while communicating via RS485
2-wire, this parameter sets the ASD as the Master or the Follower.
2) This parameter determines the function of the ASD while operating as the
Master or the Follower. If operating as the Master ASD, an output parameter
of the Master ASD is used to control the Follower ASDs and is set here.
If operating as a Follower ASD, the ASD response when an error is incurred is
set here.
Note: Select a Follower function here if F826 is configured as a Master
Output controller for any other ASD in the system. Otherwise, an
EOI failure will result.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
0 — Follower (Decel Stop If Error Detected)
1 — Follower (Continues Operation If Error Detected)
2 — Follower (Emergency Off If Error Detected)
3 — Master (Frequency Command)
4 — Master (Output Frequency)
5 — Master (Torque Reference)
6 — Master (Output Torque)
Direct Access Number — F806
Parameter Type — Selection List
Factory Default — Follower (Decel Stop)
Changeable During Run — Yes
Frequency Point Selection
Program Communications Communication Reference Adjust
This parameter is used to set the communications reference for scaling.
See F811 — F814 for additional information on this parameter.
Note: Scaling the communications signal is not required for all
applications.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
0 — Disabled
1 — RS485 (2-Wire — NOT USED)
2 — RS485 (4-Wire)
3 — Communication Option Board
Direct Access Number — F810
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
F806 F810