P9 ASD Installation and Operation Manual 221
Communications Option (DeviceNet/Profibus) Setting 8
Program Communications Communication Settings
While using the DeviceNet/Profibus communications protocol, F841F846
allow the user to select the ASD memory location that holds the Command/
Frequency/Monitoring instructions to be applied to the ASD for
Communications Option Settings 813, respectively.
See the DeviceNet Option Instruction Manual (P/N 58683) for additional
information on this parameter.
Settings:
0 — Disabled
1 — FD01 (ASD Status 1)
2 — FD00 (Output Frequency, 0.01 Hz)
3 — FD03 (Output Current, 0.01%)
4 — FD05 (Output Voltage, 0.01%)
5 — FC91 (ASD Alarm)
6 — FD22 (PID Feedback Value, 0.01 Hz)
7 — FD06 (Input Terminal Status)
8 — FD07 (Output Terminal Status)
9 — FE36 V/I
10 — FE35 (RR Input)
11 — FE37 (RX Input)
12 — FD04 (Input Voltage [DC Detection], 0.01%)
13 — FD16 (Real-Time Speed Feedback
14 — FD18 (Torque, 0.01%)
15 — FE60 (My Monitor)
16 — FE61 (My Monitor)
17 — FE62 (My Monitor)
18 — FE63 (My Monitor)
19 — F880 (Free Notes)
20 — FD29 (Input Power, 0.01 kW)
21 — FD30 (Output Power, 0.01 kW)
22 — FE14 (Cumulative Operation Time, 0.01=1 Hour)
23 — FE40 (FM Terminal Output Monitor)
24 — FE41 (AM Terminal Output Monitor)
Direct Access Number — F841
Parameter Type — Selection List
Factory Default 0000h
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 9
Program Communications Communication Settings
See F841 for information on this parameter.
Direct Access Number — F842
Parameter Type — Selection List
Factory Default 0000h
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 10
Program Communications Communication Settings
See F841 for information on this parameter.
Direct Access Number — F843
Parameter Type — Selection List
Factory Default 0000h
Changeable During Run — Yes
Communications Option (DeviceNet/Profibus) Setting 11
Program Communications Communication Settings
See F841 for information on this parameter.
Direct Access Number — F844
Parameter Type — Selection List
Factory Default 0000h
Changeable During Run — Yes
F841 F844