232 P9 ASD Installation and Operation Manual
My Function Time Data 4
Program My Function My Function Data
This parameter is used to set the response delay of the My Function Time
Data 4 terminal.
The applied discrete input signal must be present at the input terminal of the
P9 ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F931
Parameter Type — Numerical
Factory Default 0.01
Changeable During Run — Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 5
Program My Function My Function Data
This parameter is used to set the response delay of the My Function Time
Data 5 terminal.
The applied discrete input signal must be present at the input terminal of the
P9 ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F932
Parameter Type — Numerical
Factory Default 0.01
Changeable During Run — Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Count Data 1
Program My Function My Function Data
This parameter is used to set the pulse-count threshold value used to trigger the
discrete output COUNT1 (ON Timer).
COUNT1 (ON Timer) outputs a 1 upon reaching the threshold setting of this
parameter.
Direct Access Number — F933
Parameter Type — Numerical
Factory Default 0
Changeable During Run — Yes
Minimum — 0
Maximum — 9999
Units — Pulses
My Function Count Data 2
Program My Function My Function Data
This parameter is used to set the pulse-count threshold value used to trigger the
discrete output COUNT2 (ON Timer).
COUNT2 (ON Timer) outputs a 1 upon reaching the threshold setting at this
parameter.
Direct Access Number — F934
Parameter Type — Numerical
Factory Default 0
Changeable During Run — Yes
Minimum — 0
Maximum — 9999
Units — Pulses
Input Function Target 1
Program My Function My Function Unit 4
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Input Function Target 1
terminal.
This setting assigns the function of the programmable Input Function Target 1
terminal to any one of the user-selectable functions listed in
Table 8 on pg. 250,
Table 9 on pg. 251, or Table 11 on pg. 253.
See F977 for additional information on this parameter.
Direct Access Number — F935
Parameter Type — Selection List
Factory Default 0 (Disabled)
Changeable During Run — Yes
F931 F935