P9 ASD Installation and Operation Manual 41
Command Control Selections
The following is a listing with descriptions of the
Command Mode (F003) selections (Program
Fundamental Standard Mode Selection Command
Mode Selection).
Settings:
0 — Terminal Block
Allows for Command control input via the
Terminal Board.
2 — EOI Keypad
Used for EOI command control.
3 — RS485
Used to transfer commands to the ASD via 4-wire RS485.
4 — Communication Option Board
Use this setting if using the optional Communication Board for command control.
Frequency Control Selections
The following is a listing with descriptions of the
Frequency Mode (F004) selections (Program
Fundamental Standard Mode Selection Frequency
Mode 1).
Settings:
1 — V/I
Used when a 0 to 10 VDC analog input or a
0 – 20 mADC current input is used as the speed control input. Only one input signal type may be
used at a time. Set SW301 to the desired input signal type.
2 — RR
Used for a 0 to 10 VDC analog input signal.
3 — RX
Used for a -10 to +10 VDC analog input signal.
5 — EOI Keypad
Used for EOI frequency control.
6 — RS485
Used to transfer speed commands to the ASD via 4-wire RS485.
(Default)
(Default)