92 https://www.toshiba.com/tic/
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Input Terminal 16 (LI8) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the LI8 discrete
input terminal.
In addition, this input terminal must be specified as Normally
Open or Normally Closed.
This setting assigns the function of the programmable LI8 termi-
nal to one of the user-selectable functions listed in Table 9 on
page 252.
Note: The Expansion IO Card Option 2 option board (P/N
ETB004Z) is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N
58686) for additional information on the function of this terminal.
Direct Access Number
F126
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
Always ON Terminal Function 2
Program Terminal Input Terminals
This parameter is used to set the functionality of the virtual dis-
crete input terminal Always ON Terminal Function 2. As a virtual
terminal, this control terminal exists only in memory and is con-
sidered always to be in its True (connected to CC) state.
It is often practical to assign a function to this terminal that the
user desires to be maintained regardless of external conditions or
operations.
This parameter sets the programmable ON terminal to one of the
user-selectable functions listed in Table 9 on page 252.
Direct Access Number
F127
Parameter Type — Selection List
Factory Default — (ASD-Depen-
dent)
Changeable During Run — No
Always ON Terminal Function 3
Program Terminal Input Terminals
This parameter is used to set the functionality of the virtual dis-
crete input terminal Always ON Terminal Function 3. As a virtual
terminal, this control terminal exists only in memory and is con-
sidered always to be in its True (connected to CC) state.
It is often practical to assign a function to this terminal that the
user desires to be maintained regardless of external conditions or
operations.
This parameter sets the programmable ON terminal to one of the
user-selectable functions listed in Table 9 on page 252.
Direct Access Number
F128
Parameter Type — Selection List
Factory Default — (ASD-Depen-
dent)
Changeable During Run — No