EasyManua.ls Logo

Toshiba Q9+ - Page 108

Toshiba Q9+
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
96 https://www.toshiba.com/tic/
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Input Terminal 1 (F) Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the ASD to any change in
the F terminal input by the programmed value.
The delay may be increased to provide additional electrical noise
immunity or to prevent the ASD from responding to contact
bounce or chatter.
Direct Access Number
F140
Parameter Type — Numerical
Factory Default — 8
Changeable During Run — No
Minimum — 2
Maximum — 200
Units — mS
Input Terminal 2 (R) Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the ASD to any change in
the R terminal input by the programmed value (see waveforms at
F140).
The delay may be increased to provide additional electrical noise
immunity or to prevent the ASD from responding to contact
bounce or chatter.
Direct Access Number
F141
Parameter Type — Numerical
Factory Default — 8
Changeable During Run — No
Minimum — 2
Maximum — 200
Units — mS
Input Terminal 4 (RES) Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the ASD to any change in
the RES terminal input by the programmed value (see wave-
forms at F140).
The delay may be increased to provide additional electrical noise
immunity or to prevent the ASD from responding to contact
bounce or chatter.
Direct Access Number
F143
Parameter Type — Numerical
Factory Default — 8
Changeable During Run — No
Minimum — 2
Maximum — 200
Units — mS
Input Terminal 5 – 12 Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the ASD to any change in
the 5 – 12 terminal inputs by the programmed value (see wave-
forms at F140).
The delay may be increased to provide additional electrical noise
immunity or to prevent the ASD from responding to contact
bounce or chatter.
Direct Access Number
F144
Parameter Type — Numerical
Factory Default — 8
Changeable During Run — No
Minimum — 2
Maximum — 200
Units — mS
F140F145

Table of Contents