Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 97
Input Terminal 13 – 20 Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the ASD to any change in
the 13 – 20 terminal inputs by the programmed value (see wave-
forms at F140).
The delay may be increased to provide additional electrical noise
immunity or to prevent the ASD from responding to contact
bounce or chatter.
Direct Access Number —
F145
Parameter Type — Numerical
Factory Default — 8
Changeable During Run — No
Minimum — 5
Maximum — 200
Units — mS
Output Terminal 10 (R3) Function
Program Terminal Output Terminals
This parameter sets the functionality of the R3 output terminal to
any one of the user-selectable functions listed in Table 12 on
page 257.
In addition, the output terminals must be specified as Normally
Open or Normally Closed.
See the instruction manual for the 16-Bit BIN/BCD option for
additional information on the function of this terminal.
Direct Access Number —
F168
Parameter Type — Selection List
Factory Default — Always OFF
Changeable During Run — No
Output Terminal 11 (R4) Function
Program Terminal Output Terminals
This parameter sets the functionality of the R4 output terminal to
any one of the user-selectable functions listed in Table 12 on
page 257.
In addition, the output terminals must be specified as Normally
Open or Normally Closed.
See the instruction manual for the 16-Bit BIN/BCD option for
additional information on the function of this terminal.
Direct Access Number —
F169
Parameter Type — Selection List
Factory Default — Always OFF
Changeable During Run — No
Base Frequency 2
Program Motor Motor Set 2
The Base Frequency 2 setting is the frequency at which the out-
put voltage of the ASD reaches its maximum setting. The Base
Frequency Voltage 2 parameter is set at F171.
This parameter is used only when the parameters for Motor Set 2
are configured and selected. Motor Set 2 may be selected by a
properly configured input terminal (see Table 9 on page 252).
For proper motor operation, the Base Frequency should be set
for the nameplated frequency of the motor.
Direct Access Number —
F170
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — No
Minimum — (ASD-Dependent)
Maximum — (ASD-Dependent)
Units — Hz
F145 – F171