98 https://www.toshiba.com/tic/
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Base Frequency Voltage 2
Program Motor Motor Set 2
The Base Frequency Voltage 2 setting is the Motor 2 output volt-
age at the Base Frequency (F170). Regardless of the pro-
grammed value, the output voltage cannot be higher than the
input voltage.
The actual output voltage will be influenced by the input voltage
of the ASD and the Supply Voltage Compensation setting (F307).
This parameter is used only when the parameters for Motor Set 2
are configured and selected. Motor Set 2 may be selected by a
properly configured input terminal (see Table 9 on page 252).
Direct Access Number —
F171
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — No
Minimum — 50.0
Maximum — (ASD-Dependent)
Units — Volts
Manual Torque Boost 2
Program Motor Motor Set 2
The Manual Torque Boost 2 function is used to increase the low
frequency torque for high inertia loads by increasing the output
voltage at frequencies below ½ of the Base Frequency 2 setting
(F170).
See F016 (Manual Torque Boost 1) for an explanation of torque
boost.
This parameter is used only when the parameters for Motor Set 2
are configured and selected. Motor Set 2 may be selected by a
properly configured input terminal (see Table 9 on page 252).
Direct Access Number —
F172
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — %
Motor Overload Protection Level 2
Program Motor Motor Set 2
The Motor 2 Overload Protection Level parameter specifies the
motor overload current level for Motor Set 2. This value is entered
as either a percentage of the full load rating of the ASD or as the
FLA of the motor.
The unit of measurement for this parameter may be set to Amps
(A/V) or it may be set as a percentage of the ASD rating. The
nameplated FLA of the motor may be entered directly when
Amps is selected as the unit of measurement (see F701 to
change the display unit).
The Motor 2 Overload Protection Level setting will be displayed in
Amps if the EOI display units are set to A/V rather than %.
Direct Access Number —
F173
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 10
Maximum — 100
Units — %
F171 – F190