Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 205
MON2 Output Gradient Characteristic
Program Terminal Analog Output Terminals
This parameter sets the output response polarity of the MON2
output terminal. The MON2 output terminal response may be set
to respond inversely (-) or directly (+) to the input signal.
See F672 for additional information on this parameter.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number
F692
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
MON2 Bias Adjustment
Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input
signal produces a zero-level output at the MON2 terminal.
Set the assigned function of F674 to zero and then set this
parameter to a zero output.
See F674 for additional information on this parameter.
Direct Access Number
F693
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — 100.0
Units — %
Current/Voltage Display Units
Program Utilities Display Parameters
This parameter sets the unit of measurement for current and volt-
age values displayed on the EOI.
Settings:
0 — %
1 — A/V
Direct Access Number
F701
Parameter Type — Selection List
Factory Default — %
Changeable During Run — Yes
Free Unit Multiplication Factor
Program Utilities Display Parameters
This parameter provides a multiplier for the displayed speed
value shown on the EOI of the ASD.
This parameter may be used to display the rate that a commod-
ity is being processed by the driven load in process units (i.e.,
units/time).
Note: An output frequency of 100 Hz would be displayed as 50
Hz if using a multiplier of 0.5 for this parameter.
Note: PID frequency-limiting parameters are not affected by this
setting (i.e., F364, F365, F367, and F368).
Direct Access Number
F702
Parameter Type — Numerical
Factory Default — 0.00 (OFF)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.00
F692F703