Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
MON1 Voltage/Current Output Switching
Program Terminal Analog Output Terminals
This parameter is used to set the output signal type of the MON1
output terminal.
Settings
0 — -10 V – +10 V
1 — 0 – 10 V
2 — 0 – 20 mA
Direct Access Number —
F688
Parameter Type — Selection List
Factory Default — 0 – 10 V
Changeable During Run — No
MON1 Output Gradient Characteristic
Program Terminal Analog Output Terminals
This parameter sets the output response polarity of the MON1
output terminal. The MON1 output terminal response may be set
to respond inversely (-) or directly (+) to the input signal.
See F672 for additional information on this parameter.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number —
F689
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
MON1 Bias Adjustment
Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input
signal produces a zero-level output at the MON1 terminal.
Set the assigned function of parameter F672 to zero and then set
this parameter to a zero output.
See F672 for additional information on this parameter.
Direct Access Number —
F690
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — 100.0
Units — %
MON2 Voltage/Current Output Switching
Program Terminal Analog Output Terminals
This parameter is used to set the output signal type of the MON2
output terminal.
See F674 for additional information on this parameter.
Settings:
0 — -10 V – +10 V
1 — 0 – 10 V
2 — 0 – 20 mA
Direct Access Number —
F691
Parameter Type — Selection List
Factory Default — 0 – 10V
Changeable During Run — No
F688 – F692